Free tool · Portable appliance testing

How often should I PAT test?

Choose where the equipment is used, its class and what it is. You get the intervals HSE guidance suggests as a starting point.

Look for a square inside a square. If you cannot see it, treat the item as Class I.

What the HSE suggests for low-risk places

The HSE leaflet on low-risk environments such as offices, shops, some parts of hotels and residential care homes gives these initial intervals. Review them against the faults you find: if little goes wrong, you can test less often, and if a lot does, test more often.

HSE INDG236, Table 1: suggested initial intervals
EquipmentVisual inspectionInspection and test
Battery-operated (under 40 V) and extra-low voltage (under 50 V AC)None neededNone needed
Desktop computers, VDU screens2 to 4 yearsNot if double insulated, otherwise up to 5 years
Photocopiers, fax machines: not hand-held, rarely moved2 to 4 yearsNot if double insulated, otherwise up to 5 years
Class II, not hand-held, moved occasionally (fans, table lamps)2 to 4 yearsNot needed
Class II, hand-held6 months to 1 yearNot needed
Class I (kettles, some floor cleaners, kitchen equipment, irons)6 months to 1 year1 to 2 years
Cables, mains extension leads, battery chargers6 months to 4 years, depending on the equipment connected1 to 5 years, depending on the equipment connected

User checks (looking at the lead, plug and casing before use) are suggested for hand-held equipment and cables, and not for the other rows.

Why this tool does not quote the IET Code of Practice

The 4th edition of the IET Code of Practice for In-service Inspection and Testing of Electrical Equipment had a table of suggested initial frequencies. The IET has said that table "has now disappeared in the 5th edition and has not been replaced", and that the interval should come from a risk assessment. So the intervals above come from HSE guidance, which is free to read and still current.

Sources

Questions people ask

Is PAT testing a legal requirement?

Not in itself. The HSE says the law does not make inspection or testing of electrical appliances a legal requirement. It requires an employer to make sure electrical equipment is maintained so that it does not cause danger. How you do that, and how often, depends on the equipment and where it is used.

How often should office equipment be PAT tested?

HSE guidance for low-risk places such as offices and shops suggests, as a starting point, a formal visual inspection every 2 to 4 years for IT equipment and for double-insulated items that are not hand-held. Earthed (Class I) items like kettles are suggested a visual inspection every 6 months to 1 year and a combined inspection and test every 1 to 2 years. These are initial intervals to review against what you find.

Does every appliance need a PAT test?

No. HSE says not every electrical item needs a portable appliance test. For some equipment a user check and a visual inspection is enough. Double-insulated (Class II) equipment that is not hand-held generally does not need a combined inspection and test in low-risk settings, and battery-operated equipment under 40 volts needs neither.

What is the difference between Class I and Class II equipment?

Class I equipment relies on an earth connection for safety, so the earth needs testing. Class II equipment is double insulated and usually marked with a square inside a square. HSE says that if you cannot see that symbol you should assume the item is Class I and carry out a portable appliance test.

What about construction sites, hire companies and schools?

They are not low-risk environments in the HSE leaflet, which names offices, shops, some parts of hotels and residential care homes. HSE says a power tool used on a construction site should be examined more frequently than a lamp in a hotel bedroom, and recommends that equipment suppliers formally inspect and test hired equipment before each hire. HSG107 gives suggested frequencies for these settings. This tool gives no figure for them because we could not verify one.

Did the IET Code of Practice remove the table of test intervals?

Yes. The 4th edition had a table of suggested initial frequencies. The IET has said that the table disappeared in the 5th edition and has not been replaced, and that intervals should instead come from a risk assessment covering the environment, users, equipment type, frequency of use and previous records. This is why the intervals here come from HSE guidance.

Keep a PAT register that never loses a test

Plugmark is a PAT test register for testers and electricians. Every reading saves as you type, and it suggests starting intervals you can edit for each asset.

See Plugmark

Available on Android. Not currently on iPhone.

This tool is free and runs in your browser. Nothing you enter is sent anywhere. Overpass Limited is a software company, not an electrical contractor, and this is general information, not advice. Ask a qualified electrician about your own installation.